RTU-710T

RTU-710T

Radio Slave Station TETRA

On-off inputs:
The module's 16 opto-isolated on-off inputs can be connected in groups of 4 for +ve or -ve polarity. Each input is assigned a 16-bit counter that can be used as a time totalizer or event counter at up to 10 pulses/sec, if and as required.

On-off outputs:
The on-off outputs are opto-isolated PNP transistors (+ve switching) rated for loads up to 500 mA, 12-24 VDC.

Analog inputs:
These inputs accept 0-20 mA or 4-20 mA sensor/transmitter signals that are digitized with 12-bit resolution.

I/O Expansion:

RTU-710T modules have an I/O expansion bus interface through which Type PEM I/O Expansion Modules can be connected, to increase the I/Os available. Every time the RTU module is started up, it automatically scans this bus interface to check what Expansion Modules are connected, and their I/O configurations.



Technical Data: RTU-710T
Radio Slave RTU Stations with On-Off and Analog I/O

Funktion: TETRA remote I/O station with on-off and analog inputs,
and on-off outputs.
RF transmit
power level
Pout : 1 Watt
Frequency range: Tetra Standard
On-off inputs:

16 on-off inputs, opto-isolated,potential-free. Auxiliary functions: Time totalizer function available on 8 inputs Event counter function available on 8 inputs
On-off outputs: 8 (optionally 16) on-off outputs, PNP, opto-isolated, potential-free
Analog inputs:

4 analog inputs,
0-10 VDC / 0-20 mA / 4-20 mA Auxiliary functions: · Minimum value (valley) detection Maximum value (peak) detection Averaging
I/O expansion interface:: Supports up to 16 daisy-chained Type PEM I/O Extension Modules
RF field strength indication: LED bar-graph display of received RF signal strength.
Power supply voltage: 12 - 24 VDC +/- 20%
Enclosure:

Aluminum pressure die-cast housing,
DIN rail mounting.
Protection class: IP-65
Dimensions
without clip
80 x 162 x 62 mm
Operating temperature: -20ºC to +70ºC